A clouded sight glass is hard to read from across the unit. Flashing makes a float rise and fall as gas expands beneath it. A control system without a level signal has no measurement to act on. The SOR Measurement and Control 1100 Series magnetic level indicator (MLI) addresses all three. Your process sets the right configuration. This post covers each configuration choice and where it fits.
How the SOR 1100 Series MLI Works
Process liquid flows into the chamber through the process connections. A float inside rises and falls with the level in the vessel. The float carries a magnet, and this magnet turns color-coded flags in an indicator external to the chamber. It also actuates magnetic switches and transmitters attached to the chamber. Adding an external instrument leaves the pressure boundary intact.
Core Configuration Options
Chamber Style and Process Connections
Start with the chamber style, since six styles cover the common mounting needs. Side-mounted chambers come sealed, bottom flanged, top flanged, or flanged at both ends. Top-mounted chambers come with a removable float or a sealed float. Flanged ends give you access to the float for service.
Process connections come as NPT, socket weld, or flanged, from 1/2 inch to 3 inches. Flanges follow ANSI B16.5 or EN 1092-1, in slip-on or weld neck styles. Chamber size runs from 2 inches to 4 inches.
Materials and Process Ratings
The standard chamber is 316/316L stainless steel. Other chamber materials include 304 stainless steel, Hastelloy C, titanium, and Inconel 625. Additional alloys are available on request. The float is titanium as standard, with 316 stainless steel as an option.
Check your process against the ratings. The SOR 1100 Series handles full vacuum to 4,000 psi and temperatures from -320°F to 1,000°F. Minimum specific gravity is 0.39.
Indicator and Flag Options
Three indicators cover different temperatures and viewing needs. Glass suits temperatures up to 1,000°F, while impact-resistant polycarbonate suits temperatures up to 450°F. The patented Vista™ indicator matches the 450°F limit and adds a 200° viewing angle while still maintaining a viewing distance of 250 feet or greater.
An insulation pad allows higher temperatures on the polycarbonate models. Consult the factory if you need them, and read the Vista™ indicator product bulletin(PDF) for details.
Flag colors follow temperature limits. Yellow and black work to 600°F, and orange and black work to 650°F. Red and white work to 1,000°F. A custom etched stainless steel scale shows the units or markings you specify.
Measuring Range and Length
Standard measuring ranges run from 12 inches to 18 feet. Longer ranges are available on request, and tall vessels take stacked units joined by flanges. An extension of the chamber bottom can also be ordered to accommodate long, low specific gravity floats.
Certifications and Testing
Certification options include NACE MR0175 compliance and a Canadian Registration Number (CRN). PED 2014/68/EU is also available. Certificates of conformance cover ASME B31.1 power piping and ASME B31.3 process piping. A CRN requires one of them. Testing options range from hydrostatic test certificates and positive material identification to radiographic, ultrasonic, and dye penetrant examination. The inspection and testing certifications bulletin(PDF) explains the options.
For safety-critical service, read our post on how to design and integrate magnetic level indicators for critical service.
Options for Demanding Conditions
Flashing and Boiling Protection
Gas expanding beneath a float makes it rise and fall quickly. Thousands of fine bubbles rising around the float sometimes sink it. Flashing and boiling protection uses an oversized chamber with a baffle plate and springs at the top and bottom. The baffle keeps the float aligned with the indicator while vapor escapes around it. See the flashing and boiling product bulletin(PDF) for the design.
Cryogenic Insulation and Frost Extension
Light hydrocarbons flash to vapor when temperature control slips. Cryogenic insulation helps hold the process between 32°F (0°C) and -300°F (-184°C). The build uses 2-inch-thick closed-cell polyisocyanurate foam under a waterproofing membrane and sealed aluminum cladding. An acrylic frost extension keeps frost off the indicator, so operators still read the flags. The cryogenic design bulletin(PDF) covers the full build.
Insulation Blankets and Heat Tracing
For high temperatures, removable insulation blankets cover either the chamber or the chamber and flanges. Steam or electric heat tracing protects against freezing or holds temperature in the chamber.
Interface Detection
An interface float tracks the boundary between two immiscible liquids when their specific gravities differ by 0.20 or more. Give the upper and lower specific gravity values when you order. When measuring interface, the chamber requires at least three connections to the vessel to accurately equilibrate the process.
Float Failure Detection
This option extends the indicator 6 inches below the lower process connection and inverts the flag colors there. Inverted colors show when a float has failed.
Magnetic Particle Trap
Some older vessels shed ferromagnetic particles. The particles collect on the float magnets, and the added weight causes measurement faults. A magnetic particle trap on the bottom process connection catches them before they reach the float. You clean the trap during preventive maintenance, so you clean the float less often.
Corrosive Environments
Corrosive fluids attack metal parts over time. Acids, caustics, brines, and chlorinated fluids wear chamber walls, floats, and process connections. A leak creates a safety risk and a cleanup cost.
Magnetic level indicators suit these services. The float stays sealed inside the chamber, and the indicator stays outside the process. The magnetic coupling reads the level through the chamber wall. Only the chamber and the float touch the fluid.
Material selection decides how long the instrument lasts. Stainless steel is the standard choice for most applications. Specify a corrosion-resistant alloy when stainless steel is not compatible with your fluid. Use CPVC primarily when the process is corrosive and none of the standard materials will work. CPVC resists many acids and caustics. It has lower temperature and pressure limits than metal, so confirm your process conditions before you select it.
Instruments to Pair With the MLI
Instruments attach to the outside of the chamber, so one unit gives you both visual indication and electronic measurement. SOR assembles and calibrates them with the chamber before shipping.
Point Level Switches
Magnetically coupled switches strap to the chamber and give you high and low level alarms or pump control. You move or replace a switch without opening the chamber. SOR also pairs the MLI with additional chambers and other point level technologies. Options include the SOR 1510 float switch, the SOR ULS 2700 ultrasonic switch, and the SOR 660 capacitance switch.
Magnetostrictive Level Transmitter
The SOR 1310 magnetostrictive level transmitter attaches with non-ferrous mounts, so you install it without opening the chamber. It sends a 4-20 mA analog signal with HART communication to your control system. You set PLC alarms from the mA output. Its local LCD display shows level at a finer resolution than the flags do. If the visual indication fails, the transmitter still reports level.
For more detail, read our post on how a magnetostrictive level transmitter works with an MLI.
Guided Wave Radar
A guided wave radar probe shares the chamber with the float. The float gives visual indication, and the radar gives a 4-20 mA output. A baffle plate separates the float from the probe, so the two technologies work independently. SOR builds the chamber to your specification. The guided wave radar product bulletin(PDF) shows the chamber design.
Differential Pressure Transmitter With Remote Seals
A differential pressure transmitter with remote seals adds continuous level measurement, with analog and HART signals to the control system. It works independently of the MLI, so damage to one leaves the other measuring. Seal options suit a range of process connections and liquids, and SOR assembles and calibrates the system in house.
Applications for the SOR 1100 Series MLI
The SOR 1100 Series serves oil and gas, chemical and petrochemical, and power generation plants. It also serves pulp and paper, food and beverage, pharmaceutical, and wastewater plants. The five applications below show the options working together.
Sight Glass Replacement
Sight glass is often original to the plant. Over time the glass clouds, so the level is hard to read from a distance. Glass also tends to leak and break. The SOR 1100 Series replaces it directly. Process liquid stays separate from the indicator, so clouding and entrapped process do not affect the reading.
Learn more in our When to Replace a Sight Glass with a Magnetic Level Indicator: A Safety-First Guide.
Midstream Gas Processing
Flashing and boiling upset floats in midstream gas processing. This design uses a baffle plate and springs to protect the float. For liquefied gas and refrigeration processes, add cryogenic insulation and a frost extension.
Storage Tanks With Long Measuring Ranges
One customer monitored a kerosene tank with a segmented armored sight glass on a bridle. Contact with the kerosene clouded the glass and made readings difficult. SOR supplied a 20 foot center to center MLI, about 22 feet overall. The unit eliminated the external bridle. Long units ship as stacked sections joined by flanges and assemble on site, which avoids shipping one long unit. Read the full kerosene tank application note(PDF).
Power Generation: Condensate Collection Tank
Internal corrosion affected the sight glass on a condensate collection tank. Pneumatic pressure switches handled the alarms and controlled the pumps moving condensate out of the tank. An MLI gave visual indication unaffected by the corrosion. External level switches adjust from outside the chamber and drive the alarms and pumps through the DCS. SOR matched the MLI to field measurements of the tank connections and supplied a custom insulation blanket. Read the full condensate collection tank application note(PDF).
Two-Liquid Interface Service
Two liquids with different specific gravities, such as oil and water, often share one vessel. Interface control keeps the bottom liquid from carrying over with the top liquid. An interface float tracks the boundary, and a magnetostrictive transmitter adds a continuous signal for control.
Frequently Asked Questions
Q. Do I Need to Open the Chamber to Add a Switch or Transmitter?
A. No. Magnetically coupled switches and the magnetostrictive transmitter attach to the outside of the chamber, so the pressure boundary stays intact.
Q. Does the Visual Indication Need Power?
A. No. The float magnet turns the flags through magnetic coupling, so the level stays readable during a power loss.
Request a Quote for Your Application
Send your application details to SOR Controls Group, and they will help you match the configuration to your process. Each unit needs these details:
- Maximum pressure
- Maximum process temperature
- Process specific gravity
- Chamber material
- Chamber type and configuration
- Process connection type and configuration
- Center-to-center dimension
Additional Resources on the SOR Measurement and Control 1100 Series Magnetic Level Indicator
Options and Instruments to pair with the SOR 1100 Series MLI
- 1100 Series MLI Catalog (Form CAT1596)(PDF)
- 1100 Series MLI Engineered for Challenging Applications (Form 1877)(PDF)
- 1100 Series MLI Flashing and Boiling Bulletin (Form 1839)(PDF)
- 1100 Series MLI Cryogenic Design (Form 1867)(PDF)
- 1100 Series MLI with CPVC (Form 1968)(PDF)
- 1100 Series MLI with Magnetostrictive Level Transmitter (Form 1833)(PDF)
- 1100 Series MLI for Guided Wave Radar (Form 1926)(PDF)
SOR 1100 Series MLI Application Notes
- Kerosene Tank Level (Form 1849)(PDF)
- Small Specific Gravity Applications (Form 1937)(PDF)
- Slug Catcher Liquid Measurement (Form 1720)(PDF)
- Slug Catcher Level Measurement (Form 1726)(PDF)
- Separator Level Indication (Form 1730)(PDF)
- Feedwater Heater Level (Form 1758)(PDF)
- Condenser Hotwell (Form 1804)(PDF)
- Condensate Collection Tank for a Pulp and Paper Plant (Form 1746)(PDF)
- Boiler for a Sugar Mill (Form 1878)(PDF)