Smart Pressure Transmitters for Process Pressure, Differential Pressure, and Level

Smart Pressure Transmitters: Pressure, Differential, Level

At a remote well site, a smart pressure transmitter reports to a terminal unit over Modbus. On a solar-powered sand recovery vessel, another runs on low power. A refinery uses them to track the gas left in its calibration cylinders, and Modbus keeps the wiring short. A power plant added measurement points to a panel with no room for a full-size transmitter. A petrochemical plant needed an alarm the moment a rupture disc burst. A dust collector needed its pressure drop watched.

Water systems rely on them as well. In a city holding tank, a level signal starts and stops the pumps. At a municipal well, a level signal shuts the pump off before the well runs dry.

 

Smart Pressure Transmitters in the Field

Wellsite Remote Monitoring

An independent oil and gas producer ran a supervisory control and data acquisition system for its wells. The system needed Modbus RTU over RS-485 on its instruments. Four SOR Measurement and Control 815PT transmitters with ±0.1% accuracy measured tubing, casing, horizontal separator, and heater treater pressure. They sent data by Modbus to a local remote terminal unit. The site then sent the data wirelessly to a remote server. Read the Remote Monitoring application note (PDF)(PDF).

Solar Powered Sand Recovery

A company monitored large high-pressure vessels used to recover fracking sand. The sites ran on solar power and needed HART. The solution used the SOR Measurement and Control 815PT. The 1-5 VDC low power mode kept power use low while the unit still provided HART 7 communication. Read the Sand Recovery for Fracking Operation application note (PDF)(PDF).

Boiler Feed Water With Local and Remote Readout

A combined cycle power plant needed boiler feed water pressure on a local indicator and over 4-20 mA. The plant also wanted HART for diagnostic data at its programmable logic controller. A diaphragm seal protected the line from scale buildup. The team retrofitted the SOR Measurement and Control 815PT and the local indicator to share one diaphragm seal process connection. Read the Boiler Feed Water application note (PDF)(PDF).

Rupture Disc Overpressure Alarm

A petrochemical plant monitored a safety valve and rupture disc with a digital pressure switch. The switch gave false alarms, and the plant wanted better corrosion resistance. The SOR Measurement and Control 815PT replaced it. The built-in switch output alerts the plant when the rupture disc bursts. The 4-20 mA HART output adds continuous pressure measurement. The 316 stainless steel body resists corrosion. Read the Safety Valve and Rupture Disc application note (PDF)(PDF).

Tank Level on a Chemical Injection Skid

A chemical injection skid injects corrosion inhibitors into oil wells. The skid might sit in remote locations without power, so it needed a low-power level measurement. The SOR Measurement and Control 815DT with ±0.1% accuracy measured pressure at the bottom of the tank. The tank top has a vent, so the low side vents to atmosphere. The customer needed no local indicator. Read the Chemical Injection Skid application note (PDF)(PDF).

More Application Notes

Other notes cover continuous emissions monitoring(PDF) and auxiliary steam pressure(PDF). More cover a cyclone separator(PDF), storm water levels(PDF), and municipal wells(PDF).

 

Match the Problem to the Feature

Here is what each job needed and which feature delivered it.

If you need Look for Seen in
Every instrument on the network to speak Modbus Modbus RTU over RS-485 communication Wellsite remote monitoring
Low power use with HART on a solar-powered site 1-5 VDC low power mode with HART 7 Sand recovery
A local reading and a remote 4-20 mA signal, with HART diagnostics 4-20 mA output with HART 7 and a diaphragm seal process connection Boiler feed water
An overpressure alarm and a continuous reading at one point A configurable switch output with a 4-20 mA HART output and a 316 stainless steel body Rupture disc alarm
Level in a remote tank with low power use Differential pressure measurement with the low side vented to atmosphere Chemical injection skid
Level corrected for water temperature changes A differential pressure transmitter paired with a 1400 Series temperature transmitter assembly Water level temperature fluctuations
A range change at the transmitter External magnetic zero and span Any installation

 

 

Choosing the Right Features

These jobs depend on a few choices you make before you order.

Smart or Basic Transmitter

A basic transmitter sends one 4-20 mA signal. A smart transmitter adds a microprocessor and a digital link. The link lets you read the measurement and check diagnostics. You change settings from the control room or with a handheld communicator. Choose a smart transmitter when you need any of those. The boiler feed water plant wanted HART diagnostic data at its programmable logic controller. A basic transmitter does not send it.

HART 7 or Modbus RTU

HART 7 carries digital data on the same two wires as the 4-20 mA signal. It suits a plant with existing 4-20 mA loop wiring and a HART-capable control system. Modbus RTU runs over an RS-485 serial network. It suits a remote terminal unit or controller already on Modbus. The wellsite producer required Modbus on its instruments. The sand recovery and boiler feed water sites chose HART.

Built-in Switch Output or a Separate Switch

A switch output turns an alarm or control action on and off at a set point. A built-in switch output gives you the alarm and the continuous reading from one instrument at one process connection. The petrochemical plant in the rupture disc application replaced a digital pressure switch this way. SOR Measurement and Control 815 transmitters offer nine switch modes, listed in the specifications table below.

Setting Zero and Span at the Transmitter

Sometimes the range has to change while you stand at the transmitter. SOR Measurement and Control 815 transmitters use external magnetic zero and span for this. Two magnetic targets sit on the housing: a circle for zero and a triangle for span. To set zero, bring the pressure to the zero value. Hold a magnet on the circle for 3 seconds, then remove it. Repeat on the triangle at the span value. The unit needs power and a pressure source during setup, and almost any magnet works.

You set the range anywhere within the pressure range of the sensor. A 0-2500 psi sensor ordered with zero at 200 psi and span at 2300 psi ships with those points. You reset them later at the housing.

Measuring Level With Pressure

A smart level pressure transmitter turns pressure into liquid level. It calculates level from the weight of the liquid above the sensor and the specific gravity of the liquid. It reports level digitally over HART or Modbus, alongside a 4-20 mA signal. Two SOR Measurement and Control 815 models measure level, one from inside the liquid and one from outside the vessel.

The SOR Measurement and Control 815LT hangs in the liquid on its cable. It measures hydrostatic pressure in vented tanks, sumps, reservoirs, and slurry. The catalog lists water and wastewater, lift stations, lime slurries, leachate tanks, chemical storage tanks, clarifiers, and digesters. Read our post on using a submersible level transmitter in water and wastewater systems for well and stormwater detail.

The SOR Measurement and Control 815DT mounts outside the vessel. In an open tank, connect the high side to the tank bottom and vent the low side to atmosphere. The reading equals the liquid head. In a closed tank, connect the low side to the vapor space above the liquid so tank pressure cancels.

Add a temperature measurement when liquid density shifts. Water expands as it warms, so the level rises without a change in pressure. A thermal power plant paired the SOR 815DT with a 1400 Series temperature transmitter assembly on a water storage tank. The control system used the temperature to compensate the level reading. Read the Water Level Temperature Fluctuations application note (PDF)(PDF).

 

The SOR Measurement and Control 815 Series Smart Pressure Transmitters

The jobs above used SOR 815 Series transmitters. The series is a family of smart pressure transmitters in a 316 stainless steel housing. Each model offers analog 4-20 mA output with either HART 7 or Modbus communication and a configurable switch output. You configure each unit in the field. An external magnet sets zero and span at the housing, and HART or Modbus sets them remotely.

Each unit is loop-powered. It reports 4-20 mA with HART 7, or 1-5 VDC in low power mode. Modbus RTU over RS-485 is also available. You select the output in the field. Units ship with 4-20 mA active unless you request otherwise, and only one analog output is active at a time.

Where the SOR Measurement and Control 815PT, SOR 815DT, and SOR 815LT Fit Best

Pick the model by what you measure: process pressure, differential pressure, or submersible level.

SOR 815PT for High Pressure

The SOR 815PT measures process pressure from 0-5 psi to 0-30,000 psi. Absolute ranges of 0-15, 0-50, and 0-100 psia are also available. Above 10,000 psi, the unit uses an Autoclave F250C connection. For dirty or paraffin media, a flush mount, liquid-filled 316L diaphragm seal is available on selected ranges. The wellsite, sand recovery, boiler feed water, and rupture disc jobs above all used the SOR 815PT.

SOR 815DT for Differential Pressure, Flow, and Level

The SOR 815DT measures differential pressure from 0-5 psid (0-138 inches of water) to 0-500 psid. The maximum static line pressure is 1,000 psi. Turndown is 5:1, and the output is linear by default, with square root output for flow. The unit measures 2.2 inches face-to-face and weighs 1.8 pounds. The chemical injection skid above used the SOR 815DT on an open tank.

SOR 815LT for Submersible Level

The SOR 815LT is a submersible level pressure transmitter. It measures hydrostatic pressure through a vented cable, carries an IP68 rating, and submerges to 1200 feet. Standard ranges are 0-35, 0-115, and 0-575 feet of water column. Custom ranges start at 7 feet, and higher or lower ranges are available on request. Hang the SOR 815LT in the liquid. A cable clamp holds the cable in place, and a remote display shows the reading.

 

All three models share the same outputs, switch output, magnet setup, and 3-year warranty.

Model Measures Standard ranges Housing Agency approvals Display
SOR 815PT Process pressure, including absolute ranges 0-5 psi to 0-30,000 psi. Absolute: 0-15, 0-50, 0-100 psia 316 stainless steel, explosion-proof, NEMA 4X, IP66 FM, ATEX/IECEx. CRN and Dual Seal on selected ranges Local LCD
SOR 815DT Differential pressure, level, and flow 0-5 psid (0-138 inches of water) to 0-500 psid 316 stainless steel, explosion-proof, NEMA 4X, IP66 FM, ATEX/IECEx. Dual Seal on selected ranges Local LCD
SOR 815LT Submersible level through hydrostatic pressure 0-35, 0-115, 0-575 feet of water column. Custom from 7 feet 316 stainless steel, IP68, submersible to 1200 feet No agency approvals Remote LCD

 

Tell SOR Controls Group about your application, and the team will match a model to it.

 

Request a Quote
Find a Rep

 

Specifications and Options

Full details are in the Pressure Transmitters Catalog (Form CAT1806)(PDF).

Specifications

Item
SOR Measurement and Control 815 Series
Output 4-20 mA or 1-5 VDC low power, software selectable. Units ship with 4-20 mA active.
Communication HART 7 or Modbus RTU over RS-485. A HART device descriptor file is available for download.
Switch output Normally open solid-state relay rated 30V and 120mA. Nine modes: off, windowed normally open, windowed normally closed, single point normally open, single point normally closed, pulse width modulation pulsed low, pulse width modulation pulsed high, dead band normally open, and dead band normally closed. The output opens when power is removed. Zero and span points, switch mode, and set points are set at the factory as you specify. A HART communicator changes the switch configuration later.
Supply voltage 10 to 36 VDC, or 18 to 36 VDC with the LCD display
Loop resistance 667 ohms at 24 VDC
Response time Under 70 milliseconds
Accuracy ±0.25% of upper range limit as standard, including linearity, hysteresis, and repeatability. The High Accuracy option improves it to ±0.1%.
Long-term stability ±0.5% of upper range limit per year
Temperature effect ±1% of upper range limit per 100°F from -40 to 176°F
Temperature ranges Compensated and ambient: -40 to 176°F (-40 to 80°C). Process: -40 to 194°F (-40 to 90°C).
Overpressure SOR 815PT: 3 times full scale up to 0-100 psi, 2 times from 0-250 to 0-10,000 psi, and 1.4 times above. SOR 815DT and SOR 815LT: 3 times full scale.
SOR 815PT connection and materials 1/2 inch NPT male with a 1/4 inch NPT female port. Wetted parts are 316/316L stainless steel up to 0-50 psi for absolute ranges, and 17-4 stainless steel above 0-50 psi. Above 10,000 psi, an Autoclave F250C female connection for 1/4 inch outside diameter tubing replaces the NPT threads. A flush-mount, liquid-filled 316L diaphragm seal on selected ranges suits dirty, sticky, or high particulate media such as paraffin.
SOR 815DT connection and materials 1/4 inch NPT female on the high and low sides. Wetted parts are 316/316L stainless steel. Thread adapters, direct and remote mount diaphragm seals, tri-clamp fittings, flanged connections, and other styles are available on request.
Local display The IN option adds a 5-digit backlit LCD in an explosion-proof housing. Push buttons configure the display, and the display and transmitter configure separately. The SOR 815LT uses a remote-mounted display.

 

Options

Option
Detail
Hazardous locations (SOR 815PT and SOR 815DT) FM explosion-proof for Class I, II, and III, Division 1, Groups A to G, temperature class T5, Type 4X. FM nonincendive for Class I, II, and III, Division 2. ATEX and IECEx flameproof Ex db IIC T5 Gb, IP66. INMETRO approval is also available. The SOR 815LT carries no agency approvals.
Dual Seal FM approval on selected ranges. The Dual Seal version is not hermetically sealed. Standard units use hermetically sealed leads.
Sour service NACE MR0175/ISO 15156 certification with the diaphragm seal process connection. Consult the factory for other ranges.
Oxygen service Cleaned for industrial oxygen service
Certificates Calibration, hydrostatic pressure test, inspection report, compliance and conformance, typical material of wetted parts, certificate of origin, and manufacturer’s certification
SOR 815LT sensor types Standard: stainless steel 1/2 inch NPT male with a 1/4 inch NPT female port, for frequent or continuous immersion. Second: removable PVC self-flushing nose cone for relatively clean fluids. Third: 2.5-inch stainless steel diaphragm seal with a protective cage for sludge and slurry.
SOR 815LT cable Polyurethane jacket with a vent tube to reference atmospheric pressure. Specify the length in feet. A cable clamp for suspension mounting is available. IP68, submersible to 1200 feet.
Engineered-to-Order Every SOR product is available Engineered-to-Order. Range, materials, process connections, and output configuration match your application. Factory calibration is free.

 

Read our post on specifying pressure transmitters in hazardous areas to match a protection concept to your area classification. The Agency Certification List (Form 2045)(PDF) lists each certificate.

 

Frequently Asked Questions

Q. What Is a Smart Pressure Transmitter?

A. A smart pressure transmitter combines a pressure sensor with a microprocessor. It reports pressure over a digital protocol such as HART or Modbus. You configure it remotely. The SOR 815 Series also lets you set zero and span with a magnet at the housing.

Q. How Do I Set Zero and Span on SOR 815 Transmitters?

A. Hold a magnet on the circle target on the housing for 3 seconds to set zero. Hold it on the triangle target to set span. Apply power and a pressure source first. You can also set zero and span with HART or Modbus.

Q. What Outputs Does the SOR 815 Series Offer?

A. SOR 815 Series transmitters offer 4-20 mA with HART 7, 1-5 VDC low power, and Modbus RTU over RS-485. Each model also has a configurable switch output. One analog output is active at a time.

Q. Which SOR 815 Model Measures the Highest Pressure?

A. The SOR 815PT. It measures process pressure up to 0-30,000 psi. The SOR 815DT reaches 0-500 psid with a 1,000 psi maximum static line pressure.

Q. Does the SOR 815DT Measure Level?

A. Yes, the SOR 815DT measures level along with differential pressure and flow. In an open tank, connect the high side to the tank bottom and vent the low side to atmosphere.

Q. Which Models Carry Hazardous Location Approvals?

A. The SOR 815PT and SOR 815DT carry FM and ATEX/IECEx approvals. The SOR 815LT carries no agency approvals.

Q. How Accurate Is the SOR 815 Series?

A. SOR 815 Series accuracy is ±0.25% of the upper range limit as standard. The High Accuracy option improves it to ±0.1%.

Q. Does SOR Calibrate the Transmitter Before Shipping?

A. Yes, SOR factory calibration is free. Give the zero and span points when you order.

Q. Are SOR 815 Transmitters Available Engineered-to-Order?

A. Yes, you specify the range, materials, process connections, and output configuration, and SOR builds the transmitter to match.

Q. What Warranty Do the SOR 815 Models Carry?

A. Each SOR 815 model carries a 3-year warranty.

 

Request a Quote for Your Application

Send your application details to SOR Controls Group. The team will match the model and configuration to your process. Each unit needs these details:

  • Model: SOR Measurement and Control 815PT, SOR 815DT, or SOR 815LT
  • Measurement type: process pressure, absolute, differential, or submersible level
  • Pressure range, with zero and span points
  • Output and communication
  • Switch mode and set points, if used
  • Process connection and wetted material, or seal type
  • Agency approval required
  • Display option
  • For the SOR 815LT: sensor type and cable length

 

Request a Quote
Find a Rep

Additional Resources on the SOR Measurement and Control 815 Series Smart Pressure Transmitter

Product Pages

  1. SOR 815PT Smart Pressure Transmitter
  2. SOR 815DT Smart Differential Pressure Transmitter
  3. SOR 815LT Submersible Smart Level-Pressure Transmitter

Catalogs and Instructions

  1. Pressure Transmitters Catalog (Form CAT1806)(PDF)(PDF)
  2. SOR 815LT Submersible Level Transmitter Catalog (Form CAT1735)(PDF)(PDF)
  3. SOR 815PT General Instructions (Form GI1571)(PDF)(PDF)
  4. SOR 815DT General Instructions (Form GI1588)(PDF)(PDF)
  5. SOR 815LT General Instructions (Form GI1741)(PDF)(PDF)
  6. Agency Certification List for Pressure Transmitters (Form 2045)(PDF)(PDF)
  7. SOR 815 HART Device Descriptor (ZIP)

SOR 815 Series Application Notes

  1. SOR 815PT: Remote Monitoring of Casing, Tubing, Horizontal Separator and Heater Treater Pressures at Oil & Gas Well Sites (Form 1586)(PDF)(PDF)
  2. SOR 815PT: Sand Recovery for Fracking Operation (Form 1715)(PDF)(PDF)
  3. SOR 815PT: Boiler Feed Water Application (Form 1719)(PDF)(PDF)
  4. SOR 815PT: Continuous Emissions Monitoring (Form 1721)(PDF)(PDF)
  5. SOR 815PT: Safety Valve & Rupture Disc Overpressure Alarm System (Form 1723)(PDF)(PDF)
  6. SOR 815PT: High and Low Pressure in Auxiliary Steam System (Form 1724)(PDF)(PDF)
  7. SOR 815DT: Chemical Injection Skid (Form 1716)(PDF)(PDF)
  8. SOR 815DT: Monitoring Pressure Drop on Cyclone Separator (Form 1749)(PDF)(PDF)
  9. SOR 815DT: Transmitters Measure Water Level Temperature Fluctuations (Form 1752)(PDF)(PDF)
  10. SOR 815LT Storm Water Levels (Form 1791)(PDF)(PDF)
  11. SOR 815LT Municipal Wells (Form 1792)(PDF)(PDF)