Level Measurement Methods: How to Choose for Your Process

SOR Level Measurement Products

Level measurement keeps a process in control. Each job calls for a point level signal, a continuous signal, or a visual reading at the vessel.

The right method depends on the vessel. The fluid, the pressure, the temperature, and the condition of the surface are all necessary considerations. This post walks through the main methods and the two hardest conditions, flash boiling and turbulent media. It then shows the level instruments SOR Measurement and Control builds.

 

 

Start with pressure: differential pressure for level measurement

Differential pressure transmitters measure level. A column of liquid creates pressure at the bottom of a vessel. The transmitter compares this pressure with a reference and reports level. The piping setup depends on the vessel.

  • Open tank. Connect the transmitter high-pressure side to the tank bottom. Vent the low-pressure side to atmosphere. The reading equals the liquid head.
  • Closed tank. Connect the low-pressure side to the vapor space above the liquid. Tank vapor space pressure then cancels out.
  • Density changes. Level equals differential pressure divided by specific gravity. This needs a known, consistent specific gravity for the liquid. If the specific gravity shifts, the level reading shifts.

Differential pressure transmitters also measure flow when you select a square root output. Our post Smart Pressure Transmitters for Process Pressure, Differential Pressure, and Level covers setup, ranges, and options in full.

 

 

 

Methods of Level Measurement

Level instruments fall into three groups. Point level instruments, such as switches, signal when liquid reaches a set height. Continuous instruments report level across the full range. Magnetic level indicators show level on the vessel itself.

Method
How it measures
Watch for
Float A float rides the liquid surface and moves a switch or transmitter Float sizing depends on the specific gravity of the fluid
Displacer A partly submerged displacer senses buoyant force Density changes alter the reading, so specific gravity matters
Differential pressure The transmitter measures the pressure of the liquid head Level needs a known, consistent specific gravity. Wet reference legs need maintenance and risk leaks
Non-contacting ultrasonic Sound pulses travel to the surface and back Foam, contamination, and beam spread affect the reading
Contacting ultrasonic Sound crosses a gap in the probe, and liquid in the gap changes the signal The probe senses point level only. Buildup in the gap affects the reading
RF capacitance A probe senses the change in capacitance as liquid covers it The probe must suit the application
Magnetostrictive A float magnet interacts with a wire. The transit time of the resulting wave gives float position Float sizing depends on specific gravity. Foam does not affect it, because the float sinks through foam and rides on the liquid
Magnetic level indicator A float magnet drives flags outside a sealed chamber Flash boiling and ferromagnetic particles disturb the float

 

 

 

 

The hard level measurement cases: flash boiling and turbulent media

Flash boiling

Flash boiling happens when a liquid loses pressure or gains heat and turns to vapor. Bubbles form inside the liquid. Light hydrocarbons flash when temperature control slips. A churning surface and bubbles make a steady reading harder for several methods.

A float-based instrument faces two specific problems. Gas expanding beneath the float makes it rise and fall quickly. Fine bubbles rising around the float sink it.

SOR builds the SOR 1100 Series magnetic level indicator for these conditions. This specific chamber configuration is oversized, with a baffle plate and springs at the top and bottom. The baffle keeps the float aligned with the indicator while vapor escapes around it. The flashing and boiling bulletin(PDF) gives the details.

For cryogenic and light hydrocarbon service, SOR adds about 2 inches of closed-cell polyisocyanurate foam. A waterproofing membrane and sealed aluminum cladding cover the foam. This helps hold the process between 32°F (0°C) and -300°F (-184°C). An acrylic frost extension keeps frost off the indicator. The cryogenic design bulletin(PDF) covers this build.

Turbulent and foaming media

Turbulence moves the surface and weakens signals bounced off it. Many users settle the reading with a bypass pipe or a stilling well. A bypass chamber gives an instrument the same benefit.

The SOR 1000 Series engineered bypass chamber reduces turbulence at the instrument. It also lets operators isolate the instrument for maintenance. For foam, a magnetostrictive float sinks through the foam and rides on the liquid. The SOR 1310 uses this principle.

Other hard conditions

  • Two liquids. An interface float follows the boundary when the specific gravities differ by 0.20 or more. You provide the upper and lower specific gravity when you order. The chamber needs at least three vessel connections.
  • A magnetic particle trap on the bottom process connection catches ferromagnetic particles before they reach the float magnets.
  • Float failure. The indicator extends 6 inches below the lower process connection with inverted flag colors. The colors show when a float has failed.

Read more in 1100 Series MLI Engineered For Challenging Applications(PDF).

 

 

 

The SOR Measurement and Control level measurement line at a glance

SOR builds level switches and transmitters with float, displacer, ultrasonic, RF capacitance, magnetostrictive, and differential pressure methods. It also builds magnetic level indicators, bypass chambers, and flushing rings. Each product is available Engineered-to-Order.

Product type Models What it does
Level switches SOR 1510, 1530, 1540, 1550, 1710, 2700, 660, 300 Series, 100 Series Sends high and low alarms and runs pump control
Level transmitters SOR 1310, 670, 510LT, 510SF, 815LT, 1800DP, 815DT Sends a continuous level signal to your control system
Magnetic level indicators SOR 1100 Series (1110, 1120, 1130) Shows level on the vessel and carries added switches and transmitters
Engineered bypass chambers SOR 1000 Series Houses an instrument off the process line
Level flushing rings SOR 1010FR Clears buildup in front of a transmitter diaphragm

 

 

 

Level measurement switches: choose the sensing method, then customize

Each sensing method suits different fluids and conditions.

You can customize any SOR Measurement and Control level switch. Options include float or displacer type, vertical or horizontal orientation, flanged or sealed chambers, and extreme-temperature versions. Carbon steel and stainless steel are standard. Exotic materials(PDF) are available.

Many models carry ATEX, CSA, IECEx, and SIL approvals. Each model’s product page lists its ratings.

 

 

 

Level Measurement transmitters: choose the signal you need

A level transmitter sends a 4-20 mA signal in proportion to level. Output options also include 1-5 VDC with Modbus, 4-20 mA with HART, and a single-point electric switch. SOR tailors every level transmitter to your requirements, and a variety of probes are available.

  • The SOR 1310 measures up to 20 feet. A later section shows how it pairs with the SOR 1100 Series.
  • Differential pressure. The SOR 815DT and the SOR 1800DP measure level as a pressure difference. The 1800DM and 1800RM are also differential pressure units with remote seals.
  • RF capacitance. The SOR 670 gives a continuous signal up to 150 feet.
  • The SOR 510LT and 510SF are hydrostatic and cover 10 to 463 feet of water column. The SOR 815LT is a submersible smart level-pressure transmitter.

The SOR 815DT covers ranges from 0-5 psid (0-138 inches of water) to 0-500 psid. You set the range anywhere within the sensor range, by HART or with an external magnet on the housing. Outputs are 4-20 mA with HART 7, 1-5 VDC, and Modbus RTU. Standard accuracy is ±0.25% of upper range limit, and the High Accuracy option improves it to ±0.1%. Housing and wetted parts are 316/316L stainless steel. Direct and remote mount diaphragm seals are available on request. SOR engineers range, materials, connections, and output to order.

The SOR 1800DP covers spans from -0.87 to +0.87 psid up to -72.5 to +1450 psid. Accuracy is ±0.075% of full scale. Outputs are 4-20 mA with optional HART, 1-5 VDC, and Modbus. The product page lists an integral LCD. Manifolds with 3 or 5 valves are available. Remote seals are available on the 1800DM and 1800RM models.

Both transmitters carry ATEX and IECEx approvals. The 815DT adds FM and the 1800DP adds CSA. The product pages list the full approvals.

 

 

Magnetic level indicators: add switches and transmitters outside the chamber

The SOR 1100 Series magnetic level indicator uses a float and a magnet to show level. The process stays inside the chamber. The patented Vista™ indicator(PDF) gives a 200° viewing angle and 250 feet of visibility.

Our post Magnetic Level Indicator Configurations and Applications covers chamber, material, and indicator options. If you plan to replace a sight glass, read When to Replace a Sight Glass with a Magnetic Level Indicator.

You then add devices to the outside of the chamber. The pressure boundary stays intact.

  • Magnetostrictive transmitter. The SOR 1310MAG gives you a continuous level signal. The next section covers it.
  • Point level switches. These strap to the chamber for high and low alarms or pump control. Choose the SOR 1510 float switch, the SOR 2700 ultrasonic switch, or the SOR 660 capacitance switch.
  • Differential pressure transmitter with remote seals. It measures level on its own, independent of the indicator, with analog and HART signals.

 

 

 

Pair the SOR Measurement and Control 1310MAG with the SOR Measurement and Control 1100 Series

The SOR 1310MAG magnetostrictive level transmitter detects level through the magnetic field of a float. The SOR 1100 Series float carries a magnet. The 1310MAG mounts to the outside of the chamber on non-ferrous mounts. Installation and removal are easy. The SOR 1310NET is our direct insertion model for tank applications.

  • Up to 20 feet.
  • ±0.032 inches (±0.813 mm).
  • 4-20 mA with HART.
  • Top level and interface level.
  • Display and setup. A local LCD and the Quick-Cal function for simple recalibration.

The pairing gives one chamber three jobs. The indicator shows level at the vessel. The 1310MAG sends a continuous signal to your control system. Point level switches add alarms and pump control. The chamber stays closed throughout.

Our post What Is a Magnetostrictive Level Transmitter and How Does It Work With an MLI explains the principle. The 1100 Series MLI with Magnetostrictive Level Transmitter bulletin(PDF) shows the assembly.

 

 

 

Bypass chambers and flushing rings

The SOR 1000 Series engineered bypass chamber houses an instrument off the process line. You avoid complex piping. Chambers are serviceable or sealed.

Magnetostrictive transmitters, RF capacitance level controllers, mechanical level switches, and pressure transmitters all mount on a chamber. SOR has more than 30 years of chamber manufacturing experience and designs custom chambers for new or existing piping.

The SOR 1010FR level flushing ring installs between a transmitter and a standard ASME flange. It clears buildup in front of the diaphragm without disconnecting the transmitter. Each ring has one or two connections to drain piping, take samples, or bleed a valve. It works with flanged, pancake, and inline diaphragm seals.

 

 

 

How to build your level measurement system

  1. Define the job. Decide whether you need an alarm, a continuous signal, local indication, or all three.
  2. List your conditions. Note the fluid, specific gravity, pressure, temperature, vessel size, and any hazardous area approval. Note flashing, turbulence, foam, or particles.
  3. Choose the sensing method and the mounting style. The Product Selector narrows the models.
  4. Choose the output signal your control system reads.
  5. Add a chamber, an indicator, or a flushing ring where the application calls for one.

 

 

 

Frequently asked questions

Q. Do I need to open the chamber to add a switch or transmitter to a magnetic level indicator?

A. No. External switches and the SOR Measurement and Control 1310MAG transmitter attach to the outside of the chamber. The process stays sealed.

Q. Which continuous transmitter pairs with the SOR Measurement and Control 1100 Series?

A. The SOR Measurement and Control 1310MAG magnetostrictive transmitter mounts to the outside of the chamber. A differential pressure transmitter with remote seals is also an option.

Q. Which is better, a float or a displacer?

A. The better choice depends on the fluid and the conditions. SOR Controls Group builds both, so you choose the one that fits.

Q. Does SOR Controls Group build chambers for existing piping?

A. Yes. SOR Controls Group designs custom chambers for new or existing piping.

Q. Does SOR Controls Group offer special materials?

A. Yes. Carbon steel and stainless steel are standard on level switches. Exotic materials are available from SOR Controls Group.